Sunwin 3750kVA Resistive/Reactive Load Bank (WN-3750L)

1. Product Overview

In the deployment and maintenance of diesel generators, gas generators, and backup power systems, no-load testing alone is far from enough to prove true reliability. To comprehensively evaluate the performance of power systems under real-world conditions, Sunwin — a professional load bank supplier and manufacturer — introduces the 3750 kVA Resistive/Reactive (RL) Load Bank (Model: WN-3750L). Specifically designed for Factory Acceptance Testing (FAT), Site Acceptance Testing (SAT), on-site commissioning, full-load testing, step-load testing, and annual maintenance, this containerised load bank is the ultimate tool for rigorous generator validation, aligned with the requirements of prevailing international testing standards such as ISO 8528 and NFPA 110.

By combining resistive and inductive loads, this load bank accurately simulates real-world operating conditions with a Power Factor (PF) of 0.8 lagging, aligning with the common requirements of most generator sets and prevailing international testing standards.


2. Core Advantages: Built for High-Capacity, High-Precision Testing

2.1 Standard 0.8 Lagging Power Factor

The standard 0.8 lagging power factor (PF 0.8 lagging) matches the operating characteristics of most generator sets and prevailing international testing standards. Adjustable resistive and inductive load steps enable comprehensive performance evaluation at various load percentages (0%, 25%, 50%, 75%, 100%, etc.), realistically reproducing the operating behavior of generators under resistive-inductive loads.

2.2 Broad Voltage Compatibility and Deep Customization

The unit fully supports standard generator output voltages of 400V, 415V, 480V and 690V. Custom configurations are available based on your generator’s specific rated power, current and applicable testing protocols, guaranteeing secure and reliable loading throughout the entire test cycle. As a custom RL load bank manufacturer, Sunwin delivers tailored testing solutions for a wide range of generator sets.

2.3 Containerised Design for Harsh Environments

Built with standard ISO container carbon steel and marine-grade corrosion-resistant painting, the unit features a control chamber with an IP54 (outdoor) rating and standard ISO lifting points, ensuring easy global transportation and rapid deployment — an ideal containerised load bank for power plants, data centers and overseas projects.

2.4 Superior Cooling and Safety Protections

Vertical upwards forced air cooling with 12 powerful 4kW fans (approximately 27,000 CBM/H total airflow) supports full-load operation in extreme ambient temperatures from -20°C to +60°C. Four-layer safety protections are built in: thermal emergency cut-out, airflow switch, fan overload protection, and Emergency Stop (E-stop), ensuring stability and safety throughout high-intensity, high-precision testing.

3. Main Technical Parameters

Parameter

Specification

Model

WN-3750L

Apparent Power Capacity

3750 kVA

Active Power Capacity (PF 1.0)

3000 kW

Reactive Power Capacity (PF 0.8)

2250 kVAR

Rated Testing Voltage

690Vac

Active Load Step

100kW × 6 + 200kW × 12 (Resolution: 100kW)

Reactive Load Step

75kVAR × 6 + 150kVAR × 12 (Resolution: 75kVAR)

Frequency / Phases

50Hz / 3ph 4w

Voltage Tolerance (Short Term)

+5%

Load Element Tolerance

≤ ±2.5%

Insulation Test

800Vac

Load Connections

Copper busbars

Control Voltage

3ph 690VAC 50/60Hz

Airflow Volume & Fans

Approx. 27,000 CBM/H; 12 pcs (4kW each)

Rated Ambient Temp. Operation

+60°C to -20°C

Altitude Rating

≤2000m a.s.l. (or customized)

Control Chamber IP Rating

IP54 (outdoor)

Enclosure Material

Containerised carbon steel with marine-grade painting

Dimensions (L×W×H)

7000mm × 2438mm × 2896mm (standard 20ft container size)

Maximum Weight

20,000 kg