Sunwin WN-200 200kW Resistive Load Bank
Nov 16, 2026

Sunwin WN-200 200kW Resistive Load Bank

1. Product Overview

The Sunwin WN-200 is a 200kW canopy-type resistive load bank rated at 400Vac, 50Hz, three-phase four-wire (3P4W) with a power factor of 1.0. Featuring 10 resistive load stages with 1kW fine resolution, the unit weighs only 220kg and is fitted with 4 heavy-duty castors, enabling flexible relocation and deployment in equipment rooms, workshops and outdoor sites. It is an ideal load testing tool for 200kW-class generator sets, UPS systems, energy storage systems and data center equipment.

Equipped with a Siemens SIMATIC S7-200 SMART PLC and HMI touch screen, the unit supports local operation and remote PC software control over Modbus TCP. A hardwired fail-safe trip chain and six-layer safety protection ensure the entire full-load testing process is controllable and traceable. As a professional load bank supplier and manufacturer, Sunwin offers customized configurations and quotations based on customer voltage levels, power capacity, connection methods and testing protocols.

2. Key Features

2.1 High-Accuracy Load Testing

With a minimum load resolution of 1kW, the unit combines 10 load stages (1kW, 2kW, 2kW, 5kW, 10kW, 10kW, 20kW, 50kW, 50kW and 50kW) for continuously adjustable loading up to 200kW, with a load element tolerance of ≤ ±3%. A three-phase digital meter displays voltage, current, power, frequency and power factor in real time, while the control software provides a 0–110% loading slider and segmented loading settings for refined generator and UPS performance verification.

2.2 Compact Canopy Structure, Lightweight and Mobile

The unit adopts a canopy-type structure with dimensions of 1195×1020×1100mm and a weight of only 220kg, fitted with 4 heavy-duty castors so a single operator can move it between sites. The floor-standing design is suitable for both indoor and outdoor use, making it particularly suited to space-constrained equipment rooms, test bays and on-site commissioning locations.

2.3 Industrial-Grade Resistive Elements Rated to 1200°C

The load core uses finned stainless-steel heating tubes with nickel-chromium (Ni-Cr) resistance cores rated to a temperature tolerance of 1200°C, offering high temperature resistance, oxidation resistance and long service life. Resistive load branches use Schneider or Siemens contactors with fuse protection, ensuring reliability under continuous full-load and frequent switching duty.

2.4 Smart Control System (Local & Remote)

Powered by a Siemens SIMATIC S7-200 SMART PLC, the unit performs loading, parameter setting and status monitoring locally via HMI touch screen, displaying voltage, frequency, kVA, kW, power factor and per-phase L1/L2/L3 voltage and current in real time. Remote control is available via an RJ45 Ethernet port with host software using Modbus TCP. The 10 load-stage commands drive contactors through interposing relays and a common safety permission contact, with each stage's auxiliary contact fed back to the PLC to form a complete command–execute–feedback loop.

2.5 Six-Layer Safety Protection and Fail-Safe Trip Chain

The unit is equipped with a hardwired fail-safe (normally closed) master load-trip chain: an open condition from fan overload, insufficient air pressure, chamber wall temperature reaching 120°C or Emergency Stop immediately drops the master load enable and removes all load. PLC monitoring does not replace this hardwired trip path. Six protections are integrated: fan overload protection, fan low air volume protection, thermal emergency cut-out, control circuit MCCB, local/remote control mode interlock and Emergency Stop. Fan operation with adequate air pressure is a prerequisite for load enablement.

2.6 Efficient Cooling and Robust Customizable Design

Nine 2.5kW three-phase fans with horizontal side airflow and a redundant air path provide 70m³/h of airflow per kW of load, continuously removing heat from the loading area. The exhaust side uses 304 stainless steel louvers with stainless protective grilles. With IP54 complete enclosure and IP55 control chamber ratings and a noise level of 85±3 dB(A), the structure is robust and customizable to customer requirements. Free spare parts supplied with each unit include interposing relays, fan motor protection relays, air-pressure switches, Ni-Cr heating elements and indicators/push buttons.

3. Main Technical Specifications

Parameter

Specification

Rated Power

200 kW

Power Factor

1.0

Rated Voltage

400 Vac

Frequency

50 Hz

Phase & Wires

3P4W

Load Resolution

1 kW

Voltage Tolerance (Short Term Operation)

+5%

Load Element Tolerance

±3%

Load Connection

Quick connector (Powerlink 400A, for 90-120mm² copper   conductor)

Control Power

Auxiliary

Control Voltage

400 Vac

Load Switching

3-pole contactor

Digital Meter

V/A/kW/Hz/PF

Connection Interface / Protocol

RJ45 / Modbus TCP

Local Control

HMI touch screen

Remote Control

PC-based software

Operating Temperature

-20°C to +50°C

Altitude

≤2000 m a.s.l.

Enclosure Type

Canopy

Noise Level

85±3 dB(A)

Dimensions (W×D×H)

1195×1020×1100 mm

Weight

220 kg

Airflow Direction

Horizontal

Quantity of Fans

9 (2.5kW each)

Airflow Volume

70 m³/kW/h

Portability

4 heavy-duty castors

IP Grade of Control Chamber

IP55

IP Grade of Complete Enclosure

IP54

Power Derate at Other Voltages

400Vac: 200kW; 380Vac: 180.5kW; 220Vac: 60.5kW

4. Applications

For generator sets, the unit supports factory inspection, acceptance testing and maintenance load testing of 200kW-class diesel and gas gensets, verifying output stability and protection operation at rated power. For UPS systems, it verifies full-load capability, transfer time and battery discharge characteristics. For power grids, it supports grid balancing and load regulation testing.