System Parameters |
|
Model | WN-30 |
|
Rated voltage | AC400V,3Phase,50HZ |
|
Rated power | 30kW |
|
Load steps | Load steps: 1kW, 2kW, 4kW, 8kW, 15kW; Note: 1. The heating material is an alloy resistor. When the voltage is lower than the rated voltage, the power changes according to Ohm's law. |
|
Full load accuracy | Accuracy ≤±5% |
|
Display accuracy | Inlet and outlet water temperature measurement accuracy: ±0.5℃; Pressure sensor accuracy: ± 0.5kPa ; Voltage display accuracy: 0.5 level; Current display accuracy: 0.5 level; Real-time power display accuracy: 0.5 level; Inlet and outlet water flow meter measurement accuracy: ±0.5LPM; |
|
Main circuit power interface | IEC60309 three-phase five-wire + N+E plug, 400V 63A, male socket. |
|
|
Loading method | The panel is equipped with a step switch (miniature circuit breaker) and manual loading |
|
Control power supply | Use the tested power interface (L1-N) for power supply |
|
Insulation level | AC1000V, insulation resistance ≥10MΩ |
|
Inlet water temperature | 2~100℃ |
|
Water circuit interface | Equipped with 1 liquid inlet and 1 liquid return port , using clamp -type quick connector , pipe diameter: DN25, 50.5 chuck, pipeline with exhaust valve. |
|
Pressure | The liquid cooling vessel or resistor can withstand a working pressure of 1 MPa, and the ultimate test pressure is 1.5 times the working pressure. |
|
Airtightness | No leakage for 2 hours under 1Mpa pressure |
|
Reference water flow | 0.5-5m³ / h The equipment pipeline is equipped with a built-in electric balancing valve, which can be used to adjust the flow rate and flow resistance; |
|
Cooling method | High-grade pure water cooling |
|
Insulation grade | F-Class |
|
Protection level | IP23 |
|
Duty | Continuous work |
|
Pipe material | All pipes are made of 304 stainless steel . |
|
Overtemperature protection | The load is equipped with inlet and outlet temperature monitoring, and the front display has an over-temperature alarm indicator light. When the temperature is abnormal, an alarm will be issued and the device will be unloaded (the upper limit of the inlet and outlet liquid temperature is alarmed, and the value is adjustable (the default is 80℃). |
|
Pressure protection | The load can monitor the inlet and outlet pressure of the liquid. When the pressure exceeds the set value (the alarm value can be set), an alarm will be issued and the load will be unloaded. |
|
Overload protection | Monitor the power of the whole machine during load operation. When the power exceeds the set value, an alarm will be triggered and the machine will be unloaded. The alarm value is adjustable. |
|
Short-circuit protection | When short circuit or overcurrent occurs, the step circuit breaker trips to protect against damage to the equipment; |
|
Grounding protection | The input port has a ground wire and is connected to the chassis. The chassis has a grounding position for users to use for grounding. |
|
Leakage protection | The load monitors the leakage status of the load water channel in real time. When leakage occurs, the sound and light alarm prompts and the load is unloaded. |
|
Protection switch | Some protection functions are equipped with switches, which can temporarily turn off the corresponding protection function in case of false alarm or special needs. |
|
Transportation | The front panel has a handle and the bottom has casters for easy transportation. |
|
Dimension | Volume: 6U, approximately 430mm*267mm*750mm (width*height*depth), excluding the panel handle and tail casters. The size can be adjusted and optimized appropriately . |
|
Colour | RAL2003 |
|
Weight | About 35kg |
|
Human-machine interface and display | The dummy load is equipped with a local touch screen with inlet and outlet liquid temperature display; inlet and outlet liquid pressure display; power, current, voltage display, and flow display; temperature, pressure, flow and other data display can be viewed locally , and curves and historical data can be exported to a USB flash drive. The exported data can be used to generate curves on the host computer and can be printed; |
|